SPS 321.07 NoteNote: Access to plumbing or electrical systems may be required under chs. SPS 382 to 387, Plumbing Code or ch. SPS 316, Electrical Code, Volume 2. SPS 321.07 HistoryHistory: Cr. Register, November, 1979, No. 287, eff. 6-1-80; am. Register, March, 1992, No. 435, eff. 4-1-92; am. (1), Register, November, 1995, No. 479, eff. 12-1-95. SPS 321.08SPS 321.08 Fire separation and dwelling unit separation. SPS 321.08(1)(1) Fire separation. Dwelling units shall be separated from garage spaces, accessory buildings, property lines and other dwelling units in accordance with Table 321.08 and the following requirements: 1Distance shall be measured perpendicular from wall to wall or property line, ignoring overhangs.
2 Fire rated construction shall protect the dwelling from an exterior fire source.
3 Fire rated construction may be in either facing wall.
4 Fire rated construction shall be in both facing walls.
5 The methods for garage separation in par. (a) 1. are examples of ¾ hour wall construction.
SPS 321.08(1)(a)1.1. The walls and ceiling between an attached garage and any portion of the dwelling, including attic or soffit areas, shall be ¾-hour fire-resistive construction or shall be constructed as specified in any of the following: SPS 321.08(1)(a)1.a.a. One layer of 5/8-inch Type X gypsum drywall shall be used on the garage side of the separation wall or ceiling. SPS 321.08(1)(a)1.b.b. One layer of ½-inch gypsum drywall shall be used on each side of the separation wall or ceiling. SPS 321.08(1)(a)1.c.c. Two layers of ½-inch gypsum drywall shall be used on the garage side of the separation wall or ceiling. SPS 321.08(1)(a)2.2. For all methods listed under subd. 1., drywall joints shall comply with one of the following: SPS 321.08(1)(a)2.b.b. Joints shall be fitted so that the gap is no more than 1/20-inch with joints backed by either solid wood or another layer of drywall such that the joints are staggered. SPS 321.08 NoteNote: 1/20-inch is approximately the thickness of a U.S. dime.
SPS 321.08(1)(a)3.3. Vertical separations between an attached garage and a dwelling shall extend from the top of a concrete or masonry foundation to the underside of the roof sheathing or fire-resistive ceiling construction. SPS 321.08(1)(b)(b) Structural elements exposed in an attached garage. Beams, columns and bearing walls which are exposed to the garage and which provide support for habitable portions of the dwelling shall be protected by one of the methods specified in par. (a) 1. a. or c. or other ¾ hour fire-resistive protection. SPS 321.08(1)(c)1.1. The door and frame assembly between the dwelling unit and an attached garage shall be labeled by an independent testing agency as having a minimum fire-resistive rating of 20 minutes. The test to determine the 20-minute rating is not required to include the hose stream portion of the test. SPS 321.08 NoteNote: Acceptable tests for fire rating of door assemblies include ASTM E-152, UL 10B, and NFPA 252.
SPS 321.08(1)(c)2.2. Only glazing allowed by the door’s listing may be installed in any door required under this section. SPS 321.08(1)(d)1.1. Access openings in fire separation walls or ceilings shall be protected in one of the following ways: SPS 321.08(1)(d)1.a.a. The opening is protected with a material that has a finish rating of at least 20 minutes. SPS 321.08(1)(d)1.b.b. The opening is protected in the same way as the wall or ceiling where the opening is located. SPS 321.08(1)(d)2.2. The cover or door of the access opening shall be permanently installed with hardware that will maintain it in the closed position when not in use. SPS 321.08(2)(a)(a) General. In 2-family dwellings, dwelling units shall be separated from each other and from shared tenant spaces including attics, basements, garages, vestibules and corridors. SPS 321.08(2)(b)(b) Attic separation. Dwelling units with attic space that extends over both units shall be separated in accordance with one of the following: SPS 321.08(2)(b)1.1. ‘Complete separation.’ The units shall be provided with wall construction under par. (d) that extends all the way to the underside of the roof deck. SPS 321.08(2)(b)2.a.a. The units shall be provided with wall construction under par. (d) that extends to the dwelling unit ceiling and ceiling construction under par. (e). SPS 321.08(2)(b)2.b.b. Dwelling units using this method of separation shall provide attic draft stopping under par. (f) that extends all the way to the underside of the roof deck above and in line with the separation wall. SPS 321.08(2)(c)(c) Doors. Any door installed in the dwelling unit separation shall have the door and frame assembly labeled by an independent testing agency as having a minimum fire-resistive rating of 20 minutes. The test to determine the 20-minute rating is not required to include the hose stream portion of the test. SPS 321.08(2)(d)(d) Walls. Walls in the dwelling unit separation shall be protected by not less than one layer of 5/8-inch Type X gypsum wallboard or 2 layers of ½-inch gypsum wallboard or equivalent on each side of the wall with joints in compliance with sub. (1) (a) 2. SPS 321.08(2)(e)(e) Floors and ceilings. A fire protective membrane of one layer of 5/8-inch Type X gypsum wallboard with joints in compliance with sub. (1) (a) 2., shall be provided on the ceiling beneath the floor construction that provides the separation. SPS 321.08(2)(f)1.1. Attic areas, mansards, overhangs and other concealed roof spaces shall be draft stopped above and in line with the separation wall. SPS 321.08(3)(a)1.1. Except as allowed under subd. 2., all heating and ventilating ducts that penetrate a required separation shall be protected with a listed fire damper with a rating of at least 90 minutes. SPS 321.08(3)(a)2.2. The fire damper required under subd. 1. may be omitted in any of the following cases: SPS 321.08(3)(a)2.a.a. There is a minimum of 6 feet of continuous steel ductwork on at least one side of the penetration. SPS 321.08(3)(b)(b) Electrical and plumbing components. Penetrations of a required separation by electrical and plumbing components shall be firmly packed with noncombustible material or shall be protected with a listed through-penetration firestop system with a rating of at least one hour. SPS 321.08(3)(c)(c) Plastic Piping. Penetrations of a required separation by plastic pipe shall be protected by a penetration firestop system approved by the department and installed as tested in accordance with ASTM E 814 or UL 1479, with a minimum positive pressure differential of 0.01 inch of water (3 pa), and shall have an F rating of not less than the required fire-resistance rating of the assembly penetrated. SPS 321.08 HistoryHistory: Cr. Register, November, 1979, No. 287, eff. 6-1-80; r. and recr. Register, February, 1985, No. 350, eff. 3-1-85; cr. (1m), am. (2), (5) (c) and Table, Register, January, 1989, No. 397, eff. 2-1-89; am. (2), (4) and (5) (a) (intro.), renum. (5) (b) and (c) to be (5) (c) and (d) and am. (5) (d), cr. (5) (b) and (e), (6), Register, March, 1992, No. 435, eff. 4-1-92; r. (3) (a), (5) (d), renum. (3) (b) and (c), (5) (e) to be (3) (a) and (b), (5) (d), am. (5) (a) (intro.), (6), cr. (6) (c) to (e), Register, November, 1995, No. 479, eff. 12-1-95; r. and recr. (5) and (6) (b), am. (6) (c) and (d), r. (6) (e) and cr. (7), Register, January, 1999, No. 517, eff. 2-1-99; r. (1) to (4), renum. (5) to (7) to be (1) to (3), and cr. (2) (e), Register, March, 2001, No. 543, eff. 4-1-01; corrections in (2) (c) and (d) were made under s. 13.93 (2m) (b) 7., Stats., Register, March, 2001, No. 543; CR 02-077: am. (1) (a) 1. and (2) (a) to (c) Register May 2003 No. 569, eff. 8-1-03; CR 08-043: am. (1) (intro.) and Table, r. (1) (a) 4. and (2) (e), renum. (1) (c), (2) (b), (c) and (d) to be (1) (c) 1., (2) (c), (d) and (e) and am. (2) (d), cr. (1) (c) 2., (2) (b) and (f), r. and recr. (1) (d) 1. and (2) (a) Register March 2009 No. 639, eff. 4-1-09; correction in Table 21.08 made under s. 13.92 (4) (b) 7., Stats., Register March 2009 No. 639; correction in (1) (intro.) made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; CR 15-041: am. Table 321.08, cr. (3) (c) Register December 2015 No. 720, eff. 1-1-16. SPS 321.085(1)(1) Fireblocking locations. Fireblocking shall be provided in all of the following locations: SPS 321.085(1)(a)(a) In concealed spaces of walls and partitions, including furred spaces, at the ceiling and floor levels. SPS 321.085(1)(b)(b) At all interconnections between concealed vertical and horizontal spaces including the attachment between a carport and a dwelling. SPS 321.085(1)(c)(c) In concealed spaces between stair stringers at the top and bottom of the run and at any intervening floor level. SPS 321.085(1)(d)(d) At all openings around wires, cables, vents, pipes, ducts, chimneys and fireplaces at ceiling and floor level. SPS 321.085(2)(2) Fireblocking materials. Fireblocking shall consist of one of the following: SPS 321.085(2)(c)(c) One thickness of ¾-inch nominal plywood or wood structural panel with any joints backed with the same material. SPS 321.085(2)(d)(d) One thickness of ½-inch gypsum wallboard, face nailed or face screwed to solid wood, with any joints backed with the same material. SPS 321.085(2)(e)(e) Fiberglass or mineral wool batt insulation may be used if both of the following conditions are met: SPS 321.085(2)(e)2.2. The batt shall be installed to fill the entire thickness of the opening or stud cavity. SPS 321.085(2)(f)(f) For wires, cables, pipes and vents only, non-shrinking caulk, putty mortar, or similar material may be used provided no dimension of the opening exceeds ½ inch around the penetrating object. SPS 321.085(2)(g)(g) For chimneys, fireplaces and metal vents, fireblocking shall be metal, cement board or other noncombustible material. SPS 321.085 HistoryHistory: Cr. Register, March, 2001, No. 543, eff. 4-1-01; CR 02-077: am. (1) (b) Register May 2003 No. 569, eff. 8-1-03. SPS 321.09(1)(1) A listed and labeled multiple-station smoke alarm with battery backup shall be installed in all of the following locations: SPS 321.09(1)(b)(b) On floor levels that contain one or more sleeping areas, an alarm shall be installed outside of the sleeping rooms, within 21 feet of the centerline of the door opening to any sleeping room and in an exit path from any sleeping room. SPS 321.09(1)(c)(c) On floor levels that do not contain a sleeping area, an alarm shall be installed in a common area on each floor level. SPS 321.09 NoteNote: Section 50.035 (2), Stats., requires the installation of a complete low voltage, interconnected or radio-transmitting smoke detection system in all community-based residential facilities including those having 8 or fewer beds. SPS 321.09 NoteNote: Section 101.645 (3), Stats., requires the owner of a dwelling to install a functional smoke detector in the basement of the dwelling and on each floor level except the attic or storage area of each dwelling unit. The occupant of such a dwelling unit shall maintain any smoke detector in that unit, except that if any occupant who is not the owner, or any state, county, city, village or town officer, agent or employee charged under statute or municipal ordinance with powers or duties involving inspection of real or personal property, gives written notice to the owner that the smoke detector is not functional the owner shall provide, within 5 days after receipt of that notice, any maintenance necessary to make that smoke detector functional. SPS 321.09 NoteNote: Section 101.745 (4), Stats., requires that the manufacturer of a modular home shall install a functional smoke detector on each floor level except the attic or storage area of each dwelling unit. SPS 321.09(2)(a)(a) Except for dwellings with no electrical service, smoke detectors required by this section shall be continuously powered by the house electrical service, and shall be interconnected so that activation of one detector will cause activation of all detectors. SPS 321.09 NoteNote: Wireless interconnectivity is permitted under this paragraph.
SPS 321.09(2)(b)(b) Dwellings with no electrical service shall be provided with battery-powered smoke detectors in the locations under sub. (1). Interconnection and battery-backup are not required in these dwellings. SPS 321.09(3)(3) For family living units with one or more communicating split levels or open adjacent levels with less than 5 feet of separation between levels, one smoke detector on the upper level shall suffice for an adjacent lower level, including basements. Where there is an intervening door between one level and the adjacent lower level, smoke detectors shall be installed on each level. SPS 321.09(4)(4) Smoke alarms and detectors shall be maintained in accordance with the manufacturer’s specifications. SPS 321.09(5)(5) For envelope dwellings, at least 3 smoke alarms shall be placed in the air passageways. The alarms shall be placed as far apart as possible. SPS 321.09(6)(6) In basements where two required exits are separated by a continuous wall, a smoke detector shall be placed on each side of the wall within 21 feet of each exit. SPS 321.09 HistoryHistory: Cr. Register, November, 1979, No. 287, eff. 6-1-80; r. and recr. Register, February, 1985, No. 350, eff. 3-1-85; r. and recr. Register, April, 1990, No. 412, eff. 5-1-90; renum. to be (1), cr. (2) and (3), Register, March, 1992, No. 435, eff. 4-1-92; renum. (2) and (3) to be (3) and (4), cr. (2), Register, November, 1995, No. 479, eff. 12-1-95; r. and recr. (1), r. (2), renum. (3) and (4) to be (2) and (3), and cr. (4) and (5), Register, March, 2001, No. 543, eff. 4-1-01; CR 08-043: am. (1) (b) and (3), renum. (2) to be (2) (a) and am., cr. (2) (b) and (6) Register March 2009 No. 639, eff. 4-1-09.
/code/admin_code/sps/safety_and_buildings_and_environment/320_325/321
true
administrativecode
/code/admin_code/sps/safety_and_buildings_and_environment/320_325/321/ii/08/1/d/2
Department of Safety and Professional Services (SPS)
Chs. SPS 301-399 ; Safety, Buildings, and Environment
administrativecode/SPS 321.08(1)(d)2.
administrativecode/SPS 321.08(1)(d)2.
section
true